Question 1
A 750 kW load operates at 0.78 power factor lagging. The reactive power required from capacitors to correct the power factor to 0.95 lagging is closest to:
Show answer & explanation
Correct answer: D - 355 kVAR
10 free, exam-style PE Electrical and Computer Power (PE Electrical and Computer Power) practice questions with answers and explanations. No signup required. Work through them below, then take the full free PE Electrical and Computer Power practice test to study every exam domain.
These 10 free PE Electrical and Computer Power questions are organized by exam domain, so you can see how each part of the PE Electrical and Computer Power blueprint is tested. Reveal the answer and explanation under each question.
A 750 kW load operates at 0.78 power factor lagging. The reactive power required from capacitors to correct the power factor to 0.95 lagging is closest to:
Correct answer: D - 355 kVAR
A 3/0 AWG THWN copper conductor is installed in a raceway with five other current-carrying conductors at an ambient temperature of 40°C. Using NEC Table 310.16 (75°C column = 200 A), with a temperature correction factor of 0.88 and an adjustment factor of 0.80, the adjusted ampacity is closest to:
Correct answer: B - 141 A
Per NFPA 70E Table 130.7(C)(15)(c), arc-rated PPE with a minimum rating of 8 cal/cm² corresponds to PPE Category:
Correct answer: B - 2
A 50 MVA, 138/13.8 kV transformer has an impedance of 8% on its own base. When referred to a 100 MVA system base, the per-unit impedance of the transformer is closest to:
Correct answer: C - 0.16 pu
A single-line-to-ground fault occurs on an unloaded, solidly grounded generator with sequence impedances Z₁ = j0.15 pu, Z₂ = j0.15 pu, and Z₀ = j0.05 pu. The total fault current is closest to:
Correct answer: D - 8.57 pu
A variable frequency drive operates a 460 V, 60 Hz induction motor at 45 Hz using constant volts-per-hertz control. The voltage applied to the motor is closest to:
Correct answer: D - 345 V
A 6-pole, 60 Hz, NEMA Design B induction motor operates at a full-load speed of 1,160 rpm. The percent slip at full load is closest to:
Correct answer: D - 3.3%
A transformer has a percent resistance (%R) of 1.5% and a percent reactance (%X) of 5.0%. When supplying a load at 0.80 power factor lagging, the approximate voltage regulation is closest to:
Correct answer: C - 4.2%
A transformer differential relay uses second-harmonic restraint primarily to prevent the relay from:
Correct answer: A - tripping on magnetizing inrush current
On a time-current characteristic (TCC) coordination study, the minimum coordination time interval (CTI) between two series electromechanical overcurrent relays is typically:
Correct answer: C - 0.30 to 0.40 seconds